Description
Central NA protection and coupling switch for PV systems up to 39KW/43.5KVA according to VDE-AR-N 4105:2018-11 for generation units type 2 10014057 Please note: Mains back-up fuse of type gG/gL required! (max. 100A) Mains voltage: 3 x 230/400V 50Hz Rated current: 63A (at cos phi 0.9) 56.5A (at cos phi 1) Mains type: TT- or TN-S (All-pole disconnection! ) NA-protective relay: Tele NA003-M64 Coupling switch : ABB – circuit breaker with motor reclosure Enclosure: Wall mounting, Gfk-reinforced polyester enclosure with screw cover Mounting type: Indoors or in protected outdoor area (NO direct weathering!) Protection class: IP54 Environment: max. ambient temperature 35°C! Cable entry: both bottom, both bottom, Icotek cable grommet M40 for cable 12-27mm Connections: Mains – screw terminals copper or aluminum * stranded 16mm².95mm² * copper fine stranded with AE sleeve: 10mm².70mm² Loads – screw terminals copper ONLY * solid: 10mm² * stranded: 16mm².50mm² * fine stranded. With AE sleeve: 10mm².35mm² Dimensions: approx. 360 x 720 x 201 (mm) (W x H x D) Weight: approx. 20 (Kg)
Article number : 4479
Weight | 20 kg |
---|---|
Dimensions | 20,1 × 36 × 72 cm |
Only logged in customers who have purchased this product may leave a review.
Reviews
There are no reviews yet.